 Normally closed thermostat KTO 1140 |
 Normally opened thermostat |
Application
|
Thermostats are used for controlling fan units, heaters and heat exchangers, also can be used as a signal generator for monitoring the enclosure internal temperature.
|
Technical data
Sensor element: thermal bimetal
Temperature range: +32°F to +140°F ( 0°C to 60°C), hysteresis ca. 44.6°F (7°C)
Contact types: snap action contact
Power carrying capacity: 6A (1) 125 V / 250 V AC
Radio frequency interference: N (according to VDE 0875)
Supply includes:
- thermostat,
- DIN rail,
- two holders,
- two screw clamps.
|
Note
The color of handwheel indicates type of thermostat:
Blue – thermostat is normally opened, TS-0-O
Red – thermostat is normally closed, TS-0-C
|