At workplaces where electrostatically endangered components are
processed and at which work is regularly carried out with open voltages,
such as in testing shops, an electrically conductive floor covering
must simultaneously insulate, as defined by VDE 0100. A measurement
of the resistance of a location RST is used to assess the electric insulating
power.
|
|
A lower limit to the contact resistance of a location RST for the places
cited above is prescribed in VDE 0100 / Part 410.
At places in which the rated voltage does not exceed 500 volts AC, the
resistance of a location RST must amount to at least 5 x 104 Ω. If there are
rated voltages of between 500 and 1,000 volts AC, the contact resistance
of a location must be at least 5 x 105 Ω.
Electrode surface: 96.9 in2 (625 cm2).
|