1. Offices with terminals, sales and display rooms, etc.
In these areas, a floor covering is sufficient that is antistatic according
to DIN 54 345 = < 2 kV as its voltage charge.
2. Rooms with electronic equipment, such as computer centers,
offices with special equipment, resistance to earth R2 = < 1 x 109
Ohms or voltage of charging U maximum of 2 kV.
3. Unprotected electronic components or components with
requirements for protecting people, such as testing shops in the
electronics manufacturing field, resistance to ground R2 < 1 x 108
Ohm, contact resistance of the location acc. to VDE 0100,
RST > 5 x 104 Ohm or RST > 1 x 105 Ohms (the amount of rated voltage
is decisive).
4. Unprotected electronic components or components, such as
manufacturing or laboratory rooms for making, repairing or testing
electronic equipment, subassemblies or components, resistance
to ground R2 < 1 x 108 Ohms.
5. Explosive atmospheres in general, such in potentially explosive
laboratories, gas pressure control facilities, battery storage rooms,
resistance to ground R2 < 108 Ohms.
6. In medical rooms, newly installed, R2 < 107 Ohm, in four years
R2 < 108 Ohm; HF-surgery R2 > 5 x 104 Ohms.
7. Potentially explosive substances, such as in manufacturing and
storage rooms of explosives, munitions or pyrotechnical articles,
resistance to ground R2 < 106 Ohms.
|